PRODUCT: This notice
applies to solenoid coils used on fuel pumps and shut-off valves manufactured
by Suntec Industries, Inc.
ISSUE: a number of these
coils, mostly having date codes before April of 2006, may develop an open
connection inside the coil. The internal connection on these few coils may fail
after repeated cycles of temperature expansion and contraction. During the
subsequent burner lockout and cooling of the coil, some may remake the
connection, thus disguising the problem. Please consider this possibility when
analyzing burner lockout conditions.
REPLACEMENT COILS: See
your local distributor for replacement coils, provided by Suntec under
warranty.
COIL DATE CODE: The coil manufacturing date is
specified in the small date code on the bottom side of the coil. See the
example below.
Copyright © 2002-2007 - Yaun Company Inc.
All Rights Reserved
Last Updated:05/09/2007